Cleanroom pressure control supports contamination control alongside airflow patterns, filtration, operating practices and environmental monitoring.
Regulatory Scope. Annex 1 §4.14 gives 10 Pa as a guidance value between adjacent rooms of different grades. Containment needs may require different pressure arrangements. Define the design for the actual process.
Engineering Coordination. Coordinate HVAC zoning, air balance, room leakage, doors and service penetrations. Assess the agreed pressure relationships under relevant operating conditions.
Requalification. Annex 1 §4.32 sets maximum requalification intervals of six months for Grade A/B and twelve months for Grade C/D. Plan airflow visualization for at-rest and operational conditions. Define its repeat frequency in the approved qualification programme rather than applying a universal one-to-two-year interval.
Monitoring. Under §4.16, critical pressure differences are monitored and recorded continuously; others are monitored at defined intervals. Establish alarm limits and responses through the facility’s contamination control strategy.
Review After Change. Assess facility, equipment and process changes through change control and define the appropriate requalification scope.
Conclusion. Combine pressure measurements with airflow evidence and wider contamination controls. A pressure value alone does not demonstrate sterility.
Reference: European Commission, EU GMP Annex 1 (2022), sections 4.14–4.16 and 4.32.